F-Gas Leak Check Record template
Leak check record for refrigeration and air conditioning: refrigerant charge, CO2 equivalent, method, leaks found and repair.
Opens in a free trial with this form ready to use.
Download printable PDF (68 KB)GB F-Gas Regulation (retained Regulation (EU) 517/2014); Northern Ireland: Regulation (EU) 2024/573
This template is provided as a starting point only. pro-Forms accepts no liability for the accuracy or suitability of its forms. Check every form with a suitably qualified person before using it in a live environment.
About this template
A leak check record for refrigeration, air conditioning and heat pump systems. Record the system, its refrigerant type and charge, the CO2 equivalent, whether a leak detection system is fitted and the engineer's F-gas certificate number.
Then record the check method, any leak found and where, whether it was repaired, the follow-up check date (within one month of a repair), refrigerant added or recovered and when the next check is due. The customer signs for their F-gas records.
What's on this form
Every field in the template, grouped as it appears on the phone. Required fields are marked *.
1. Equipment
- Customer name * Text
- Site name Text
- Site address Paragraph
- Job reference Text
- Date of visit * Date
- Time on site Time
- Time off site Time
- System make Text
- System model Text
- System serial number Text
- System ID / barcode Barcode scan
- System location Text
- Refrigerant type * Text
- Refrigerant charge (kg) * Text
- CO2 equivalent (tonnes) Text
- Leak detection system fitted? Yes / No Choice
- F-Gas certificate number * Text
2. Leak check
- Check method * Direct - electronic detector / Direct - bubble solution / Indirect - system parameters / Automatic leak detection Choice
- Leak found? * Yes / No Choice
- Leak location Paragraph
- Leak repaired? Yes / No / N/A Choice
- Follow-up check date (within 1 month) Date
- Refrigerant added (kg) Text
- Refrigerant recovered (kg) Text
- Next leak check due * Date
- Photo 1 Photo
3. Sign-off
- Additional comments Paragraph
- Engineer name * Text
- Engineer signature * Signature
- Date signed * Date
- Customer name (print) Text
- Customer signature Signature
Questions about this template
Which systems need a leak check?
Systems containing 5 tonnes CO2 equivalent or more of F-gas refrigerant (10 tonnes for hermetically sealed systems that are labelled as such).
How often are leak checks needed?
In Great Britain: every 12 months from 5 tonnes CO2e, 6 months from 50 tonnes and 3 months from 500 tonnes. The intervals double if a leak detection system is fitted.
What is the follow-up check?
After a leak is repaired, the system must be checked again within one month to make sure the repair was effective.