Fire Door Inspection template
Door-by-door fire door check: leaf, frame, gaps, seals, hinges, self-closer, signage and glazing.
Opens in a free trial with this form ready to use.
Download printable PDF (93 KB)Fire Safety (England) Regulations 2022; BS 8214
This template is provided as a starting point only. pro-Forms accepts no liability for the accuracy or suitability of its forms. Check every form with a suitably qualified person before using it in a live environment.
About this template
A door-by-door fire door inspection. For each door, record its location and fire rating, take a photo, then check the leaf, frame, gaps, intumescent strips and smoke seals, hinges, self-closer, latch, signage and glazing, and whether it is wedged or held open.
Each door gets a result and any remedial action, so you finish with a clear list of doors that pass and doors that need work.
What's on this form
Every field in the template, grouped as it appears on the phone. Required fields are marked *.
1. Details
- Site name * Text
- Site address Paragraph
- Date * Date
- Time Time
- Inspector * Text
2. Doors repeats as needed
- Door reference / location * Text
- Fire rating FD30 / FD60 / FD90 / FD120 / Unknown Choice
- Door photo Photo
- Door leaf undamaged * Pass / Fail / N/A Choice
- Frame secure and undamaged * Pass / Fail / N/A Choice
- Gaps 2-4mm (max 10mm at threshold) * Pass / Fail / N/A Choice
- Intumescent strips and smoke seals intact * Pass / Fail / N/A Choice
- Minimum 3 hinges, secure, no missing screws * Pass / Fail / N/A Choice
- Self-closer closes door fully from any angle * Pass / Fail / N/A Choice
- Latch engages * Pass / Fail / N/A Choice
- Signage correct * Pass / Fail / N/A Choice
- Glazing intact and fire rated * Pass / Fail / N/A Choice
- Not wedged or held open * Pass / Fail / N/A Choice
- Door result * Pass / Fail - repair / Fail - replace Choice
- Remedial action Paragraph
3. Sign-off
- Additional comments Paragraph
- Inspector name * Text
- Inspector signature * Signature
- Date signed * Date
Questions about this template
How often should fire doors be checked?
In residential buildings over 11 metres in England, communal fire doors must be checked every three months and flat entrance doors every year on a best-endeavours basis. Elsewhere, the frequency should follow your fire risk assessment.
What gap should there be around a fire door?
Typically around 3mm (between 2 and 4mm) at the top and sides. The gap under the door depends on the door's certification, often up to 10mm; check the manufacturer's data.
Can a fire door be propped open?
No, unless it is fitted with an approved hold-open device linked to the fire alarm. A wedged fire door can't do its job.