Fire Alarm Service Report mobile form preview
Fire & SecurityElectricalFacilities Management Mobile form 4 sections · 34 questions Free

Fire Alarm Service Report template

Periodic inspection and service of a fire detection and alarm system: panel, batteries, detectors, call points and sounders.

Use this template free

Opens in a free trial with this form ready to use.

Download printable PDF (74 KB)
Relates to

BS 5839-1 (periodic inspection and servicing)

This template is provided as a starting point only. pro-Forms accepts no liability for the accuracy or suitability of its forms. Check every form with a suitably qualified person before using it in a live environment.

About this template

A service report for a fire detection and alarm system. Record the panel and system category, check the log book, panel indications, batteries and charger, fault indications and remote signalling, then test field devices zone by zone.

The report records the percentage of devices tested on the visit, any variations from BS 5839-1, defects and recommendations, and confirms the system was left in normal operation, signed by the engineer and the customer.

What's on this form

Every field in the template, grouped as it appears on the phone. Required fields are marked *.

1. System

  • Customer name * Text
  • Site name Text
  • Site address Paragraph
  • Job reference Text
  • Date of visit * Date
  • Time on site Time
  • Time off site Time
  • Panel make / model Text
  • System category * Choice
  • Number of zones Text
  • Visit type * 6-monthly service / Annual service / Remedial / Callout Choice

2. Control equipment

  • Log book reviewed * Pass / Fail / N/A Choice
  • Panel indications and fault log checked * Pass / Fail / N/A Choice
  • Batteries load tested * Pass / Fail / N/A Choice
  • Charger output correct * Pass / Fail / N/A Choice
  • Fault indications tested * Pass / Fail / N/A Choice
  • Remote signalling / ARC tested * Pass / Fail / N/A Choice
  • Zone chart displayed * Pass / Fail / N/A Choice
  • Battery voltage (V) Text
  • Battery date code Text

3. Field devices repeats as needed

  • Zone / device location * Text
  • Device type * Choice
  • Result * Pass / Fail / N/A Choice
  • Notes Paragraph

4. Result

  • Percentage of devices tested this visit Text
  • System left in normal operation? * Yes / No Choice
  • Variations from BS 5839-1 Paragraph
  • Defects and recommendations Paragraph
  • Additional comments Paragraph
  • Engineer name * Text
  • Engineer signature * Signature
  • Date signed * Date
  • Customer name (print) Text
  • Customer signature Signature

Questions about this template

How often should a fire alarm be serviced?

BS 5839-1 recommends periodic inspection and servicing at intervals of no more than six months. The current edition is BS 5839-1:2025.

Does every device need testing on every visit?

No. Devices are usually tested over the course of a year, with a proportion tested each visit, so the percentage tested is recorded on the report.

What is a variation?

A deliberate departure from the recommendations of BS 5839-1, agreed with the responsible person and recorded so everyone knows about it.